HBZones | _HBZones | Honeybee zones for which you want to calculate the infiltration or ventilation rates. | Goo |
Air Flow Rate | _airFlowRate | A number representing the air flow rate into the HBZone in Air Changes per Hour (ACH). Alternatively this number can be in m3/s per m2 of exposed envelope area if the input below is set to "False." The latter is useful for infiltration, which is typically specified as a unit per area of exposed envelope. | Goo |
ACHor M3s M2 | _ACHorM3sM2_ | Set to "True" to have the airFlowRate above interpreted as ACH. Set to "False" to have itinterpreted as m3/s per m2 of outdoor-exposed zone surface area. This latter is useful for infiltration rates, which are usually defined as an intensity of flow per unit outdoor exposure. The default is set to True for ACH. | Goo |
Blower Pressure | _blowerPressure_ | A number representing the pressure differential in Pascals (Pa) between indoors/outdoors at which the specified flow rate above occurs. When set to 0 or left untouched, the specified input flow rate to this component will be the same as that output from the component (only the units will be converted and no translation from one pressure to another will occur). However, many blower door tests for infiltration occur at higher pressure differentials of 50 Pa or 75 Pa. You can input this pressure differential here in order to convert the flow rate of this blower door test to typical building pressure flow rates of 4 Pa. | Goo |